Description:

CJM8-63 Typus minimae ambitus ruptor (MCB) maxime ad tutelam contra cultrum et ambitum brevem sub AC 50Hz/60Hz adhibitum, voltage 230V/400V aestimavit, et vena aestimata ab 1A ad 63A.Etiam adhiberi potest ad commercium transitum non-frequens et in communibus adiunctis.


Product Detail

Product Tags

Construction and Feature

  • Praesidium adversus utrumque cultrum et ambitum brevem
  • Princeps brevis-circuitu facultatem
  • Securus ascendens 35mm DIN rail
  • Terminatio electrica machinis in Din rail of TH35-7.5D generis ascendet.
  • Altus brevis capacitatis brevis 6KA.
  • Circuitus custodire voluit magnum currentem ad 63A portandum.
  • Contactus positionis significatio.
  • Adhibetur ut switch principalis in familia et simili institutione.

 

Normal Service Condition

  • Altitudo supra mare planum minus quam 2000m;
  • Temperatura ambiens -5~+40, temperatura mediocris non excedens +35 intra 24 horas;
  • Relativum Umor non excedens, 50% ad maximam temperiem +40 superiorem, humiditatem relativam permisit in temperatura inferiore.Pro exemplo, relativum humiditas 90% permissa ad +20;
  • Pollutio classis: II (modo plerumque solum pollutio non-electricitatis faciendi consideratur, et etiam considerat electricitatem temporalem faciendi pollutionem interdum ex rore densato causatam);
  • Institutionem perpendicularem cum tolerantia concessa 5 .

 

Technical data

Standard IEC/EN 60898-1
Ratum Current 6A,10A,16A,20A,25A,32A,40A,50A,63A
Rated Voltage 230/400VAC(240/415)
Rated Frequency 50/60Hz
Numerus Pole 1P,2P,3P,4P(1P+N,3P+N)
OMNIBUS size 18mm
Genus curva B, C, D, Type
Refractio facultatem 4500A,6000A
Optimumoperating temperatus -5ºC ad 40ºC
Terminatio tensus torque 5N-m
Terminatio capacitas (top) 25mm²
Terminatio capacitatis (imo) 25mm²
Electro-mechanica patientia 4000cycles
Adscendens 35mm DinRail
Idoneum Busbar ACUS Busbar

 

Test Labi Type Test Current Coepi rei publicae Tempus supplantando timeor Provisior
a Tempus, mora 1.13In Frigidi t≤1h(In≤63A) Non Tripping
t≤2h(ln>63A)
b Tempus, mora 1.45In Post test t<1h(In≤63A) Tripping
t<2h(In>63A)
c Tempus, mora 2.55In Frigidi 10s Tripping
20s63A)
d B curva 3In Frigidi t≤0.1s Non Tripping
C curva 5In Frigidi t≤0.1s Non Tripping
D curva 10In Frigidi t≤0.1s Non Tripping
e B curva 5In Frigidi t≤0.1s Tripping
C curva 10In Frigidi t≤0.1s Tripping
D curva 20In Frigidi t≤0.1s Tripping

Miniature Circuit Breaker (9)

 

Quid eligas res ex CEJIA Electrical?

  • CEJIA Electrical sita in Liushi, Wenzhou -Capital urbs humilis voltage electrica producta in China. Multae variae officinae electricae producta low intentione producunt. Sicut fuses.circuit breakers.contactors.et pushbutton. Potes emere integras partes pro automationis ratione.
  • CEJIA Electrical etiam clientes praebere potest cum panelli potestate nativus. Possumus designare Mcc tabulam et invertere scrinium & scrinium starter molles secundum clientes ex icone wiring.
  • CEJIA Electrical etiam venditio internationalis rete. CEJIA producta in magna quantitate exportata sunt in Europam, Americam Meridionalem, Asiam orientalem, Medio Orientem.
  • CEJIA Electrical etiam navi eunt ad nundinas omni anno frequentandas.

 


  • Previous:
  • Deinde:

  • Epistulam tuam hic scribe et mitte nobis