Classification
- Secundum adscendens: fixum et trahere-e
- Iuxta polos: perticas tres, perticas quatuor
- Secundum vias operationis: motoria et manualia (sustentatione et reparatione)
- Secundum emissionem: intelligens super current moderatoris, sub intentione instantaneae (vel morae) emissio, et shunt emissio
- Facultas prudentium moderatoris super- current:
- classification: H type (normalis), M type (normalis intelligentis), L type (oeconomicus)
- munus cultro longa mora habet contra terminum praesidio
- unum tempus aggerari tutela munus
- functionis indication: instantiae currentis, actionis indicatio currentis, indicii singulae intentionis filum (si iubes commemorare).
- Terror munus
- Propria diagnostica munus
- Test munus
Environment Condition for Operation and Installation
- Temperatura ambiens: -5℃~ 40℃, et temperatura mediocris in 24 horis infra +35℃ (exceptis ordinibus specialibus).
- Elevatio institutionis situs: ≤2000m.
- Humiditas relativa: Non excedens 50% ad maximam ambientium temperiem +40℃.Cum temperatura inferior, permittitur superior humiditas, at infima temperatura mediocris in montn non excedente +25℃ in mense humidissimo, et maximus menstrua mediocris numiata relativa non excedente 90% in mense illo, et roribus considerationem praebens. in bona superficie, quae propter mutationem temperatus videtur.
- Tutela pollutio: 3 gradus.
- Categorias inaugurare: pro principalibus circuitibus rupti, gyros sub intentione emissionis et ambitum primi transformatorum;Ⅲ Aliorum auxiliorum circuitus et circuitus ditionis.
- Ruptores in navibus et in area tropica humida normaliter operari possunt sine impressione aeris humidi, salis nebulae et rubiginis.
- Ruptores in navibus adhibiti sub vibratione normali fideliter operari possunt.
- Praevaricator institui debet secundum stipulationes in operatione manuali.Pro praevaricatoribus, in communi usu, clivus verticalis non plus quam 50 est, eo quod in navibus usus est, clivus verticalis 22.50 non plus est.
- Ruptor in loco collocari debet ubi non est aliquod medium explosivum et pulverarium conductivum nullum gasum, quod metallum corrodet vel insulationem destruet.
- Praevaricator institui debet in cellula switchboard et postem fixa insuper debet, tutela gradus usque ad lP40.
Technical Data and Capability
Rated Tabula currentis 1 |
Rated frame current Inm A | Rated current ln A |
2000 | (400)630,800,1000,1250,1600,2000 |
3200 | 2000,2500,2900,3200 |
4000 | 3200,3600,4000 |
6300 | 4000,5000,6300 |
Brevis aestimatus ambitus frangendi facultatem et breve tempus ruptoribus resistendi, distantiae arcus "nulla" est (sicut extra ruptor arcus nulla est.) Tabula 2
Rated frame current Inm A | | 2000 | 3200 | 4000 | 6300 |
Rated modum brevem ambitum fractionis facultatem lcu(ka)O-CO | 400V | 80 | 80 | 100 | 120 |
690V | 50 | 50 | 75 | 85 |
Ratum opus brevem ambitum fractionis facultatem nx lcu(KA)/COS∅ | 400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 |
690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 |
Ratum paulisper sustinere lcw lcs(ka)O-CO-CO | 400V | 50 | 50 | 80 | 100 |
690V | 40 | 40 | 65 | 75 |
Ratum paulisper sustinere lcw (KA)—”+0.4s, O-CO | 400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) |
690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) |
Animadverte: input et extra filum positum idem sunt pro facultate solvendi. |
Maxima destruendi potestas est 360W pro praevaricatoribus, et in temperatura diversa, et currenti mutabili æstimatur. Table 3
Ambiens temperatus | Ratum current |
400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Intelligentes super current moderatoris tutelae pluma et functiones De occasum et error.Table 4
Longa mora | Brevi mora | Instantaneae | aggerari errore |
lr1 | lr2 | Error | lr3 | Error | lr4 | Error |
(0.4-1) In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) | ±15% | lnm=2000~3200A (0.2-0.8) (1200A,160A) | ±10% |
Animadverte: lf tres gradus tutelae simul habet, occasus non trans. |
Longa mora super currenti inversa temporis ooperationis lineamentis I2TL, =(1.51lr1)2tL, et actio temporis (1.02-2.0) Ir1, tempus habet error ± 15%.Table 5
1.05Ir1 | 1.3Ir1 | 1.5Ir1 S * tempus occasum | 15 | 30 | 60 | 120 | 240 | 480 |
2hno actio | -1h actio | 2.0Ir constituens tempus S * | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
Previous: CJN-250-300M60 Monocrystalline Solaris Module Deinde: CJ-219g 1-4p Modular Electrical Automatic Changeover Switch Main Switch