Product Detail
Product Tags
Technical data
| Standard | IEC60898 |
| Polonus NO. | Polonorum 1/2/3/4 |
| Rated voltage | 240/415VAC |
| Frequentia | 50/60Hz |
| Ratum current | 6,10,16,20,25,32,40,50,63A |
| vita mechanica | 10,000times |
| Praesidium gradum | IP20 |
| Munus Feature | Cum in onus / brevi circuitu praesidium |
| Perferendis caliditas | 55℃ |
| Capacitas solveret | 4/6KA |
| Rated voltage(V) | Poloni | Rated current (A) | Rated facultatem brevis circuitu solveret |
| Test fractionis facultatem (KA) | Potentia factor |
| 240 | 1 | 6,10,16,20; | 6 | 0.65~0.70 |
| 415 | 2,3,4 | 25,32,40 | 6 |
| 240 | 1,2 | 50,63 | 4 | 0.75~0.80 |
| 415 | 2,3,4 | 4 |
Current Release Dharacter Diagram
| Test current | Ratum current | Rogatus tempus | Proventus | Satus statione | Animadverte |
| (A) | (A) |
| 1.13In | Omnis | t> = 1h * | Non scandali | Cool | |
| 1.45In | Omnis | T<1h* | iter | calor | Vena ascendit valorem rogatus stabiliter in 5s |
| 2.55In | In<=32A | 1s | iter | Cool | Auxiliaris switch clausa est potentia |
| 2.55In | In> 32A | 1s | iter | Cool | Auxiliaris switch clausa est potentia |
| 5In(Cmode) | Omnis | t>=0.1s | Non scandali | Cool | Auxiliaris switch clausa est potentia |
| 10In(Cmode) | Omnis | T<0.1s | iter | Cool | Auxiliaris switch clausa est potentia |
| 10(Dmode) | Omnis | t>=0.1s | Non scandali | Cool | Auxiliaris switch clausa est potentia |
| 14In(Dmode) | Omnis | T<0.1s | iter | Cool | Auxiliaris switch clausa est potentia |
Previous: Automatic Transfer Switch for Portable Generator ATS Deinde: UKP Series IP65 Tempestas Probatur solitudinem Switch